How JCDP Capacitive Differential Pressure Transmitter Work


JCDP/JCBP Capacitive Pressure Transmitter  operates on the principle that, if the sensing  diaphragm between
two capacitor plates is deformed by a differential pressure, an imbalance of capacitance will occur
between itself and the two plates.This imbalance is detected in a capacitance bridge circuit and
converted to a D.C. output  current of 
4 to 20 mA.

 Another type of capacitor uses concentric hollow metal cylinders. The capacitance of this type just like theflat-plate type is proportional to the area.
This principle can be applied to differential pressure measurement, as shown in Figure. The pressure actingon the isolating diaphragms set up similar pressures in the silicone oil filling the space between them.
A net force proportional to the difference between the two pressures acts upon the metal sensing diaphragm and deflects it to one side or the other, depending on which input pressure is the greater.
 
he sensing diaphragm and capacitor thus form a differential variable separation capacitor. When the two input pressure are equal, the diaphragm is positioned centrally and the capacitances are equal.
A difference in the two input pressures causes displacement of the sensing diaphragm and is sensed as a difference between the two capacitances.
This change in capacitance is measured using a bridge circuit to measure the equivalent pressure signal.

BCST Introduction video

Wednesday, July 5, 2017

Cases for Wrong Installation of Electromagnetic Flowmeter

Case 1: The Flow Value Jitters Seriously. 


    
Analysis: There is pump tightly closed to the flow meter on the spot. When the liquid flows through the flow meter, it will be in the turbulent condition,
which exists strong interference in measurement. That is why the value of flow meter always jitters.
Solution: Be far away from the pump and choose the straight pipe distance, at least five times of pipe diameter longer, to guarantee the flow steady.
   As below is the similar case that is installed closed to valves.


 
 
Case 2: The Measurement Is Always Not Correct. Sometimes ATC Alarm And Lower Limit Alarm Will Occur Sometimes.



Analysis: From the picture above, there is half pipe of water inside, which means it isn’t full pipe measurement for electromagnetic flow meters.
That is why its measurement is not correct.
Solution: reduce and extend the pipe, let the liquid fulfill the pipe.
 
Case 3: The Electromagnetic Flow Meters Always Damage.




Analysis: If installed in the places where there is water immersion risk, the flow meters have to be IP68.

Solution: choose IP68

Why is the installation of electromagnetic flow meters so strict?
  1. The measurement principle of electromagnetic flow meters is based on Faraday induction, conducting medium’s cutting magnetic line generates inductive emf,
  2. and the signal is collected by the electrodes in the central axis.
That is why the liquid has to be fulfilled in the pipe, otherwise, limit alarm or Atc alarm will occur.
In which conditions will guarantee the liquid is fulfilled in the pipe?
It is surely full pipe in the vertical pipe. It is also full pipe in the horizontal pipe if installed correctly.
  1. The flow velocity of liquid through the pipe has to be uniform and stable. Why? The flow measurement is actually the product value of velocity and pipe CSA.
  2. Then if velocity is not steady, the flow measurement will jitter.
       That is why we choose to install the flow meters as far as possible. Certainly, there has to be long enough straight pipes, whose function is gentling the flow velocity
and let the liquid go through the flow meters uniformly and steadily. (5 times of pipe diameter longer upstream and 5 times of pipe diameter longer downstream)

Tuesday, June 13, 2017

High accuracy pressure sensor -silicon resistive pressure sensor


Our pressure sensor production has successfully launched in 2016 , and in the past year , our sensor has tested well and stable . The best accuracy can reach 0.05%, the standard accuracy is 0.075% . The stability and repeatibility have improved a lot comparing to capacitance type sensor .   Currently , we have sold to Iran , Russia , South Korean .  Welcome to contact us .  