Sunday, August 2, 2020

Points to Be Noted in Electromagnetic Flowmeter Engineering Application 3

12. Installation location. The electromagnetic flowmeter can be installed vertically and horizontally, but it is recommended to install vertically and the measured fluid flows from bottom to top. It can also be installed horizontally, but the two electrodes should be on the same level. When installing horizontally, ensure that the measuring tube is filled with liquid at all times. When the main pipeline is a vertical pipeline, under normal circumstances, the water flow is required to be bottom-up, try not to top-down. The latter is likely to cause relatively large flow fluctuations. In addition to the full pipe installation, this is also very important, followed by the distance of the straight pipe before and after. Choose a place that is convenient for maintenance and activities. The flowmeter should be installed at the rear end of the pump, never on the suction side: the valve should be installed on the downstream side of the flow.

13. Because the electromagnetic flowmeter measures a weak electric potential, it is necessary to eliminate all external interference to accurately measure, so good grounding is a necessary condition to ensure the stable operation of the electromagnetic flowmeter. Generally, grounding is achieved through the grounding ring or the reference electrode in the sensor and the grounding connection of the piping system.

Electromagnetic Flowmeter

14. The installation location of the flowmeter should be far away from all magnetic sources (such as high-power motors, transformers, etc.).

15. Like other flowmeters, electromagnetic flowmeters also have a protection level, usually the integrated protection level is IP65, and the split type is IP68 (for the sensor). If the customer has requirements for the installation environment of the instrument, the installation location is in an underground shady well. Or some other damp places, it is recommended that customers choose split type. In order to avoid damage caused by wrong selection.

16. Electromagnetic flowmeter can measure corrosive liquids, but the customer should provide other measurement media properties at the beginning of ordering to avoid errors in electrode selection during selection, which leads to the sensor being scrapped in the later use process, bringing inconvenience and economy to the customer on the loss.

17. Although the electromagnetic flowmeter is relatively reliable, it will not be damaged under normal circumstances, but due to its principle, the sensor electrode surface has been in contact with the liquid for a long time, and the electrode surface is more likely to be contaminated. Therefore, under normal circumstances, the electromagnetic flowmeter is recommended to be removed and cleaned once a year and a year and a half to ensure the measurement accuracy of the whole flowmeter. Any instrumentation requires "maintenance", and electromagnetic flowmeters are no exception.

The above information is provided by magnetic flow meter factory.

You can also find parts 2 and part 1 in our previous articles.

Saturday, August 1, 2020

JCLC Oval Gear Flowmeter with Pulse

JCLC Oval Gear Flowmeter with Pulse

Oval gear meters are instruments used for the continuous and intermittent measurement and control of the pipe liquid flow, which are typical of positive displacement meter, feature large flow range, low pressure loss, large viscosity range, easy installation, high accuracy and can measure high temperature, high viscosity liquids with easy calibration.

JC-LC oval gear meters are fitted with on-site pointer indication and roller integration device which can indicate the liquid flow and intermittent flow passing through the pipeline. For the different liquids (acid, alkali, salt, organic solution etc.), the meters can be made of different materials (cast iron, cast steel, stainless steel etc.). The meters are widely used for the flow measurement in the field of petroleum, chemical, chemical fiber, traffic, food industries and commerce, medical and sanitary departments.

 BCST Flowmeter with Pulse Operation Principle

Oval gear meter is generally comprised of a flow transducer and a counter mechanism. The main part of the transducer is a measuring chamber which consists of a pair of oval wheels and a sealing coupling. The counter mechanism contains speed reduction gears, adjusting device, counter, and pulse transmitter etc.

In the measuring chamber, a pair of oval wheels and cover plate make a crescent shape cavity which is used as a measuring unit. The oval wheels are rotated by the pressure difference in the inlet and outlet of the meter and drive the inlet liquid through the cavity to the outlet, each revolution of the oval wheels displaces fluid four time the volume of the cavity, the total revolutions of the oval wheels and the revolution rate will be transferred to the mechanical counter, and the total liquid volume and instantaneous flow will be known by the pointer display and the roller integration. The attached signal generator converts the rotary axial angular shift to the pulse signal and then transmits it to the electrical indicator for remote integrated flow and instantaneous flow indication and control.

Technical Parameter for BCST Oval Gear Flowmeter

1. Materials of main parts and the nominal operating pressure

JCLC-A

Cast steel

Cast iron

Stainless steel

Bronze(with oil) or rolling bearing

1.6

JCLC-E

Cast steel

Cast iron、Stainless steel

Under DN50 6.3

DN80-100  4.0

DN150-200  2.5

JCLC-Q

Cast iron

Cast iron

Alloy aluminum, engineering material

graphite

1.6

JCLC-B、C

Stainless steel

Stainless steel

Stainless steel

graphite

1.6、2.5

JCLC-L

Cast

aluminum

Cast iron,

Stainless steel

Alloy

aluminum, engineering material

Bronze(with oil)、graphite、rolling bearing

1.6

Notes:1. 0Cr18Ni12Mo2Ti for type JCLC-C; 0Cr18Ni9Ti for type JCLC-B

2. Flange is convex under 2.5MPa ,and roughness at 6.3 MPa;and both of the above at 4.0 MPa。

 

2. Accuracy        class 0.5, class 0.2 (normal operating temperature -10℃~+60℃)  

3. Measured media temp. (environment temperature -41℃~+50℃)

JCLC-A、B、C: -20℃~+60℃; 60℃~200℃(with high temp. radiator installed)

JCLC-Q、L: -20℃~+60℃;

4. Explosion-proof mark: ExiaⅡCT5, dⅡBT4

If you want to know more products of our company, please click here

https://www.bcstgroup.com/

 

Wednesday, July 29, 2020

Points to Be Noted in Electromagnetic Flowmeter Engineering Application 2

5. The electromagnetic flow transmitter should be installed in a dry and ventilated place indoors. Avoid installing it in a place with high ambient temperature. It should not be subject to strong vibration. Try to avoid equipment with strong magnetic fields, such as large motors, transformers, etc. In the case of corrosive gas, the installation site is convenient for maintenance, which is the environmental condition to ensure the normal operation of the transmitter.

6. In order to ensure that the measuring tube of the electromagnetic flow transmitter is filled with the measured medium, the variator is best installed vertically with the flow direction from bottom to top, especially for liquid-solid two-phase flow, it must be installed vertically. If only horizontal installation is allowed on site, you must ensure that the two electrodes are at the same level.

7. Valves and bypasses should be installed at both ends of the electromagnetic flow transmitter.

water-flow-meter.jpg

8. The AC potential of several millivolts measured by the electrodes of the electromagnetic flow transmitter is based on the liquid potential in the transmitter. In order to stabilize the liquid potential and keep the transmitter and fluid at the same potential, to ensure stable measurement, the transmitter shell and the metal tube should have good grounding, the converter shell should also be grounded, and the grounding resistance should not be greater than 10 Ohm, cannot be shared with the ground wire of other electrical equipment. If it is not guaranteed that the transmitter housing is in good contact with the metal pipe, use metal wires to connect them and then ground them reliably.

9. In order to avoid disturbing the signal, the signal between the transmitter and the converter must be transmitted with shielded wires. It is not allowed to put the signal cable and the power cable in parallel in the same cable steel tube. The length of the signal cable should generally not exceed 30m.

10. The installation site of the converter should avoid strong AC and DC magnetic fields and vibrations, the ambient temperature is -20~50℃, and it must not contain corrosive gases, and the relative humidity is not more than 80%.

11. In order to ensure the normal operation of the electromagnetic flowmeter and reduce the measurement error, the electromagnetic flowmeter should meet certain straight pipe requirements before and after. According to the test standard requirements of JJG 1033-2007 "Electromagnetic Flowmeter Verification Regulations", usually the front straight pipe section should reach 10D, and the rear straight pipe section should be 5D.

The above information is provided by flow instrument factory.

You can also find part 1 in our previous articles.

Friday, June 26, 2020

What Kind of End Connection Should Be Selected for Control Valve?

There are differential end connection for control valve end connection , such as  flange connection, threaded, or even welded end. Flange connection is the most common control valve end connection in the oil & gas application. Other connection such as threaded or welded end is only used in particular application.
The type of  control valve end connection shall refer to any project specification or a piping class data sheet. In general , if  valve size is over  2”, it shall have a flange connection, threaded connection is acceptable for 2” and below. Welded end control valve connection is rarely used except for an application that requires no leakage in the connection between valve and pipe line or any pipe stress consideration.
The connection between flange and valve body are preferably used an integral body flange casting. It means the control valve body and a flange, casting together so that there is no welding requirement to joint the valve and the flange.
control-valves-3.jpg
In case the sleeve control valve factory couldn’t have an integral body flange casting, as a rule of thumb used a weld neck flange that require a butt weld or full penetration weld to connect flange and valve body. Later on, this weld will require a NDE (Non Destructive Examination) Radiographic Test.
Slip on flange that use a fillet weld shall not be used because fillet weld is weaker than butt welded. Socket weld flange that use fillet weld may be used for valve 1 ½ inch and below. Even though socket weld flange also use fillet weld, but the internal weld of this flange increase the fatigue strength more than the slip on flange.
This flange is allowable for small size of control valve end connection due to difficulties of but weld perform in such size. All fillet weld connection will require a Magnetic Particle Examination or Liquid Penetrant Test.
There are three types of flange facing that will be used in the valve end connection as follow:
1. Flat Face Flange (FF Flange) :
These are used for low pressure or low valve class such as class 150 for control valve
2. Raised Face Flange (RF Flange) :
These are used for control valve class such as class 300 and class 600.
3. Ring Type Join Flange (RTJ Flange) :
These are used for high  class such as class 900 and above.

Tuesday, June 23, 2020

How to Properly Select and Maintain Vortex Flow Meters

Vortex flow meteris mainly used for flow measurement of industrial piping media such as gas, liquid, steam and other media. It is characterized by small pressure loss, large range and high accuracy, and is almost independent of fluid density, pressure, temperature and other parameters in the measurement of working condition volume flow. No movable mechanical parts, so high reliability and low maintenance. The vortex gas flow meter parameters are stable over time. The instrument adopts piezoelectric stress sensor with high reliability and can work in the operating temperature range of -25 ℃ ~ 320 ℃. There is an analog standard signal, but also digital pulse signal output, easy to use with computer digital system, is a relatively advanced, ideal flow meter. 
 1)Vortex gas oil flowmeter instrumentation is not suitable for installation in the strong vibration of the occasion is widely known to the applicant, but in the occasion of frequent changes in the magnetic field, vortex air flowmeter  will be measured above the normal value of the signal output. It has been proven that in a gas-free field, when the vortex liquid flow sensor is in a changing magnetic field, the vortex flow sensor will sense an error signal at the moment of magnetic field change and output a normal signal when the change ends and the meter is in a stable magnetic field.  
2) Coke oven gas will have moisture in the gas transmission process due to the high temperature and high humidity at the factory. The gas flow drives the water back and forth, thus creating a pulsating flow. Vortex air flowmeterin this fluid state when the output data is large or small control engineering network copyright, simply do not reflect the production conditions.  
3) Due to the coke oven gas more impurities, easy to crystallize, impurities condensed in the sensing head, resulting in measurement misalignment. As the temperature rises, impurities evaporate, sensitivity increases and the signal is enhanced; conversely, it decreases. This creates data instability.  
4) The vortex flowmeter wiring process is inaccurate, resulting in intermittent signals during transmission.  
5) The vortex flowmeterground wire does not meet the specification requirements, so that the strong power in the 50Hz interference into, when the normal signal is higher than 50Hz output normal signal, the reverse will output the wrong signal. 
Vortex Flow Meter
How to maintain 
1) In the vortex flow meter installation, connection process, should ensure the accuracy of each link, including the pre-installation inspection of the site, the installation process of the instrument wiring, system grounding wire and other aspects of the control engineering network copyright, so as to ensure the detection of real data and accurate output.   
2) For the operation of the metering system can be used "double gui metering control engineering network copyright, comparison confirmation" method, as well as "alternative method" for the operation of the metering instrument failure confirmation and troubleshooting.  
3) Periodically clean the  vortex flow meter as a whole, if necessary, blow the sensor head part of the  vortex flow meter to avoid the condensation of impurities at the sensor head. The addition of heat tracing devices to the meter section and the meter section during the cold season is also beneficial in reducing the condensation of impurities at the meter.  
4) Regular drainage of pipes, especially the moisture in front of the straight pipe section, according to the specific situation, set up a person to discharge regularly, as far as possible to reduce the moisture in the measured pipe section, to maximize the exclusion of pulsations in the fluid.  
5) Strengthen the vortex flow meter metering system data management, set up timed printing function, based on the print data combined with the production status of the instrument operation analysis.
 The above information is provided by flow instrument manufacturer.

Saturday, June 20, 2020

Pneumatic Tri-Eccentric Hard Seal Butterfly Valve Delivery

The disc of the tri-eccentric hard seal butterfly valve is installed in the diameter direction of the pipeline. In the butterfly valve body cylindrical channel, disc shaped disc around the axis of rotation, rotation Angle between 0°~90°, rotation to 90°, the valve is fully open. The characteristics of the new high life stainless steel butterfly valve and the problems in the use of the butterfly valve.
The tri-eccentric hard seal butterfly valve is widely used in metallurgy, electric power, petrochemical industry, water supply and drainage, municipal construction and other industrial pipelines where the medium temperature is no more than 425℃, for regulating the flow and cutting off the fluid.
 big-size-pneumatic-butterfly-valve
Pneumatic tri-eccentric hard seal butterfly valve is based on the two -eccentric hard seal butterfly valve to generate an angle (the sealing surface is an inclined cone), thus forming the tri-eccentric hard seal butterfly valve . The structure has no mechanical wear and scratch in the process of opening and closing , small closing torque , good cutting performance and long service lige , as well as two functions of adjustment and cutting.
This Pneumatic tri-eccentric hard seal butterfly valve is DN800 , for air application , its function for cut-off air course.   It is for one chemical industry in Southeast of China.   
The valve body is WCB , pressure is DIN 0.6 Mpa , working temperature is -60 to 200 °C  
The max size for  Pneumatic tri-eccentric hard seal butterfly valve BCST can make is DN 2000.
If you have any special requirement , we can also make based on your detail.  
pneumatic-trieccentric-butterfly-valve


Tuesday, June 16, 2020

Points to Be Noted in Electromagnetic Flowmeter Engineering Application

In the petrochemical, chemical, electric power, metallurgy, municipal, pharmaceutical and other industries, the technical difficulty and complexity of flow measurement are quite high. Research on flow measurement plays an important role in improving product quality, reducing business costs, and solving energy conservation and environmental protection. The electromagnetic flowmeter has the advantages of no resistance and no pressure loss, which can fully reduce the resistance in the pipeline and meet the requirements of energy saving and consumption reduction, so the electromagnetic flowmeter has been widely paid attention in the industry. However, although the electromagnetic flowmeter has the above advantages, and it is much better than most other types of flowmeters in reliability and stability, but in actual use, some problems will occur, the following magnetic flow meter factory will list the main points that need to be paid attention to in the application of electromagnetic flowmeter.
1. The transmitter should be installed at a position where the measurement tube can be filled with liquid at any time to prevent the illusion that the pointer is not at zero because of no liquid in the measurement tube. It is best to install it vertically to reduce the error caused by the liquid flowing through the bubble generated on the electrode. If placed horizontally, the two electrodes of the flowmeter must be kept on the same level, in order to prevent sediment or air on the top of the tube to insulate it.
KTSL-sleeve-control-valve.jpg
2. If necessary, the tube can be emptied. The built-in empty tube detection circuit will stop the accumulation and flow signal output.
3. For the fluid flowing in the anode-protected pipeline, the following points should be observed when installing the electromagnetic flowmeter: To make the fluid well grounded, a ground ring should be used; when the sensor is connected to the pipeline, there must be insulation between the flanges Insulation sleeves should also be used on the pads and screws.
4. When the electromagnetic flowmeter is installed on the grounded metal pipeline, the system potential balance is achieved through the grounding terminal on the electromagnetic flowmeter transmitter, that is, the copper core wire with a cross-sectional area of not less than 6mm2 is connected to the grounding terminal; When the electromagnetic flowmeter is installed on an ungrounded metal pipe, the two flanges are connected to the pipe flange through a copper core wire with a cross-sectional area of at least 6mm2 and are grounded. Connect the transmitter or sensor junction box to the ground terminal. Achieve system potential balance; when the electromagnetic flowmeter is installed on a plastic pipe or a pipeline with an insulating lining, the system potential balance is achieved through an additional ground ring, which is connected to the ground terminal through a copper core wire with a cross-sectional area of at least 6 mm2.